Due to scorching weather or unexpected LCW flow, the UVA QT-System was affected. The dip in LCW flow led to a rise in LCW temperature, triggering the most sensitive QT Compressors 2B and 5B. I imitated the LCW flow and temperature data from UVA elog# 579 in the table. Simultaneously, we are coordinating with the accelerator complex team to troubleshoot LCW issues in NS2.


Start DateStart TimeFinish DateFinish TimeAffected Compressor IDsLowest LCW flow during the periodQT-compressors' highest outlet Temp. (F)
2023/06/2300:002023/06/2500:002B, 5B56.3114.4
2023/07/0514:002023/07/0512:552B, 5B60100
2023/07/2612:002023/07/2812:001A58.7113.4